Description
Construction
- Conductor: Plain Annealed Copper, Class 2 Stranded Circular or Compacted
- Insulation: Cross-linked Polyethylene (XLPE), Compound
- Insulation Color : Natural
- Outer Sheath: Polyvinyl Chloride (PVC) Compound Type ST 2
- Outer Sheath Color : Black
Electrical Characteristics
- Operating Voltage, Uo/U : 0.6/1KV
- Operating Temperature : -15’C to 90’C
- Final Short Circuit Temperature : 250′ C
- Test Voltage : 3.5kV for 5 minutes
- Current Carrying Capacity
- Enclosed in conduit in thermally insulating wall etc (Ref Method A),
- 2 Cable Single-Phase A.C or D.C : 81A
- 3 or 4 Cables, 3-Phase A.C : 73A
- Enclosed in conduit on wall or in trunking, (Ref Method B)
- 2 Cable Single-Phase A.C or D.C 100A
- 3 or 4 Cables, 3-Phase A.C 88A
- Clipped Direct (Ref Method C)
- 2 Cable Single-Phase A.C or D.C : 109A
- 3 or 4 Cables, 3-Phase A.C : 99A
- Enclosed in conduit in thermally insulating wall etc (Ref Method A),
Reference Standard
- Design Specification: IEC60502-1
- Conductor: IEC60228, BS EN60228
- Flame Retardancy: IEC60332-1, BS EN60332-1
Installation Reference
- Minimum Bending Radius(mm): 8 x cable overall diameter
- Max. Pulling Tension (N/mm2) : 50
Reviews