Description
Construction
- Conductor: Plain Annealed Copper, Class 2 Stranded Circular, Compacted or Sectored
- Insulation: Cross-linked Polyethylene (XLPE) Compound
- Insulation Color :
- 2 Cores : Brown, Blue or Red, Black
- Assembly :
- Cores cabled together with filler and covered with Polyester (PET) Tape
- Insulation Color :
- Bedding : Polyvinyl Chloride (PVC) Compound Type ST2 or ST2 PVC Tape
- Bedding Color : Black
- Armour: Galvanized Steel Wire Armoured (AWA)
- Outer Sheath: Polyvinyl Chloride (PVC) Compound Type ST 2
- Outer Sheath Color : Black
Electrical Characteristics
- Operating Voltage, Uo/U : 0.6/1KV
- Operating Temperature : -15’C to 90’C
- Final Short Circuit Temperature : 250′ C
- Test Voltage : 3.5kV for 5 minutes
- Current Carrying Capacity
- Clipped Direct (Ref Method C)
- One 2-Core Cables, Single Phase A.C or D.C : 85A
- In free air or on a perforated cable tray etc, horizontal or vertical (Ref method E)
- One 2-Core Cables, Single Phase A.C or D.C : 90A
- Direct in Ground or in ducting in ground, in or around building (Ref method D)
- One 2-Core Cables, Single Phase A.C or D.C : 71A
- Clipped Direct (Ref Method C)
Reference Standard
- Design Specification: IEC60502-1
- Conductor: IEC60228, BS EN60228
- Flame Retardancy: IEC60332-1, BS EN60332-1
Installation Reference
- Minimum Bending Radius(mm): 8 x cable overall diameter
- Max. Pulling Tension (N/mm2) : 70
Reviews